• LZZW-36 Outdoor Current Transformer
LZZW-36 Outdoor Current Transformer
discuss personally
Model
LZZW-36
Basic info
Brand Wone Store
Model NO. LZZW-36 Outdoor Current Transformer
Rated voltage 33kV
Rated frequency 50/60Hz
Rated current ratio 300/5
Series LZZW
Product Detail

Product Overview

Epoxy resin casting insulation and fully enclosed support construction, encloses the primary & secondary windings and annular core in the epoxy resin casting body. The product has large periphery insulation creepage distance, withstanding dirtiness and dampness. Be suitable for measuring electric capacity, current and protective relaying in the power system of 36kV (Up to 40.5 kV).

Key Features

  • 36kV-Class Outdoor High-Voltage Adaptation Design:The LZZW-36 outdoor current transformer is engineered with a 36kV rated voltage, achieving insulation levels of 95kV for lightning impulse and 50kV for power frequency withstand voltage. It strictly adheres to GB/T 4703.2 and IEC 60044-2 standards, optimized specifically for outdoor substations, box-type substations, overhead lines, and other scenarios operating at 35kV and below. Its structural design fully accounts for the long-term operational demands of high-voltage outdoor environments, effectively resisting voltage fluctuations and insulation aging to minimize equipment failure risks caused by insulation breakdown, ensuring stable operation of the power system.

  • All-Weather Protection Structure:This product features a dual-protection barrier composed of silicone rubber composite insulation materials and a corrosion-resistant aluminum alloy enclosure. It withstands 8,000 hours of UV aging testing, enduring prolonged outdoor exposure; achieves IP68 protection for continuous operation 1.5 meters underwater, while special structural designs resist 25mm/h snowfall and 15mm ice loads. Verified by 2,500 hours of salt spray testing, it offers a creepage distance of 25mm/kV, adapting to diverse harsh outdoor environments such as coastal areas, high-altitude regions, and cold zones, thereby reducing the impact of climatic factors on device performance.

  • Dual-Winding High-Precision Measurement System:Integrating a 0.2S-class metering winding and a 5P20-class protection winding, the metering winding maintains a ratio error ≤±0.2% within 1%–120% of rated current, meeting high-precision energy metering and line loss analysis requirements. The protection winding exhibits a composite error ≤5% at 20 times rated current with a response time ≤10ms, enabling rapid triggering of relay protection devices to ensure safe disconnection during grid faults. Equipped with two sets of ratio taps (e.g., 400/5A, 600/5A), adjustable via an outdoor-sealed switch without disassembly, it adapts flexibly to varying load currents, enhancing on-site application versatility.

  • Intelligent Monitoring & Multi-Mode Communication:Embedded with sensors for temperature (-40°C–+100°C), humidity, and insulation status, the device collects real-time operational data. It supports protocols such as Modbus RTU and IEC 61850-9-2 while retaining a 4–20mA analog output, enabling seamless integration into smart grid monitoring systems or compatibility with traditional monitoring equipment. Through edge computing modules, it locally analyzes data to remotely push early warnings for anomalies, reducing outdoor inspection frequency and operational costs—ideal for intelligent management of remote outdoor equipment.

Main technical parameter

  • Rated voltage: 30 kV or 33 kV or 34.5kV or 35kV etc

  • Rated secondary current:5Aor1A

  • Rated insulation level: 36/70/170 kV (40.5/95/200 kV)

  • Standards: IEC60044-1.2003 Part 1: Instrument transformers-Part1: Current transformers

Other technical parameter pls see as follow

Single ratio

Double ratio

Remarks: Upon request we are glad to offer transformers according to other standards or with non-standard technical specs.

Outline drawing

Know your supplier
Wone Store
Main Categories
High Voltage Electrical Apparatus/Low Voltage Electrical Apparatus/Wire cable/Instrument meters/New energy/Tester/Production equipment/Generator/Electrical fittings/Integrated Electrical Equipment/Instrument Transformer/Equipment Parts
Business Type
Sales
Highest Annual Export (USD)
$300000000
Professional Experience
1 years
Workplace
1000m²
占位
占位
Related Products
Related Knowledges
Analysis of Abnormal Causes of High-Voltage Cable Grounding Circulation and Typical Cases
Analysis of Abnormal Causes of High-Voltage Cable Grounding Circulation and Typical Cases
I. Introduction to Cable Grounding Loop CurrentCables rated 110 kV and above use a single-core structure. The alternating magnetic field generated by the operating current induces a voltage on the metallic sheath. If the sheath forms a closed circuit through the earth, a grounding loop current will flow on the metallic sheath. Excessive grounding loop current (loop current exceeding 50 A, more than 20% of the load current, or a ratio of maximum-to-minimum phase current greater than 3) not only a
Felix Spark
09/03/2025
Considerations and Recommendations for Flame-Retardant Selection of High-Voltage Cables
Considerations and Recommendations for Flame-Retardant Selection of High-Voltage Cables
1.Flame-Retardant Cable Classification StandardsThe flame-retardant standard system is divided into two main categories. The first category follows the "Classification of Burning Behavior for Electric and Optical Fiber Cables" GB 31247. Cables complying with this standard system are widely used in densely populated areas such as high-speed railways and subways. This standard imposes strict requirements on parameters such as smoke density, heat release, and total smoke production, and cables typi
James
09/03/2025
Repair of high-voltage cable metallic sheaths
Repair of high-voltage cable metallic sheaths
I. Functions of Metallic Sheaths and Necessity of RepairThe metallic sheath of high-voltage cables is a metal shielding structure laid outside the insulation layer, including types such as lead sheaths, aluminum sheaths, and steel wire armor. Its core functions include mechanical protection (resisting external impact and compression), electrochemical corrosion protection (isolating moisture and soil pollutants), electromagnetic shielding (reducing electromagnetic interference to the environment)
Felix Spark
09/03/2025
What factors need to be considered when designing a transformer?
What factors need to be considered when designing a transformer?
Transformer design is a complex process that requires consideration of multiple factors to ensure safe and efficient operation. In addition, compliance with international and local regulations is essential to guarantee that transformers meet safety and performance standards. Below are key factors to consider in transformer design and the relevant regulations to follow:Transformer Design Factors: Voltage and Frequency: Determine the input and output voltage levels and the operating frequency. The
Vziman
09/02/2025
What failure modes are possible in a transformer? How to identify and fix these failures?
What failure modes are possible in a transformer? How to identify and fix these failures?
Transformers are critical components in power systems, and various failure modes can affect their operation. Timely identification and resolution of these failure modes are essential to prevent costly downtime and ensure system reliability. Below are some common transformer failure modes, along with methods to identify and address them: Insulation FailureIdentification: Insulation failure leads to decreased insulation resistance, which can be detected through insulation resistance testing (megge
Edwiin
09/02/2025
A hybrid DC circuit breaker
A hybrid DC circuit breaker
Most DC molded-case circuit breakers use natural air arc extinction, and there are typically two arc extinguishing methods: one is conventional opening and closing, where the contacts axially stretch the arc, while the conductive circuit generates a magnetic field that bends and elongates the arc, pulling it lengthwise perpendicular to the arc axis. This not only increases the arc length but also induces lateral motion, enabling air cooling to achieve arc extinction.The other method involves the